Outline of Control
ESiEN09-06 A
44
Function
6. Outline of Control
6.1
Thermostat Sensor in Remote Control (only for Z-
control)
Temperature is controlled by both the thermostat sensor in remote controller and air suction
thermostat in the AHU. (This is however limited to when the field setting for the thermostat
sensor in remote controller is set to “Use.”)
Cooling
If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote controller near the position of the user when the suction temperature is near the preset
temperature.
Ex: When cooling
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 30°C (A F):
Body thermostat sensor is used for temperatures from 18°C to 23°C (A C).
Remote controller thermostat sensor is used for temperatures from 23°C to 27°C (C E).
Body thermostat sensor is used for temperatures from 27°C to 30°C (E F).
And, assuming suction temperature has changed from 30
°
C to 18
°
C (F A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F D).
Remote controller thermostat sensor is used for temperatures from 25°C to 21°C (D B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B A).
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...