Field Setting
ESiEN09-06 A
132
Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
25 Low noise setting
Level 1 (outdoor fan with 6 step or lower)
Level 2 (outdoor fan with 5 step or lower)
Level 3 (outdoor fan with 4 step or lower)
26
Night-time low noise
operation start
setting
About 20:00
About 22:00 (factory setting)
About 24:00
27
Night-time low noise
operation end
setting
About 6:00
About 7:00
About 8:00 (factory setting)
28 Power transistor
check mode
OFF
ON
29 Capacity
precedence setting
OFF
ON
30 Demand setting 1
60 % demand
70 % demand
80 % demand
32 Normal demand
setting
OFF
ON
35
Setting of difference
in elevation for the
outdoor unit
Normal
65 m or less
90 m or less
38
Emergency
operation
OFF
Master unit operation: Inhibited
42
Emergency
operation
(prohibition of INV
compressor
operation)
Normal operation
Emergency operation
(prohibition of INV compressor
operation)
Summary of Contents for ERQ Series
Page 2: ......
Page 16: ...Combination Table ESiEN09 06 A 6 General Information...
Page 17: ...ESiEN09 06 A Specifications 7 1 Specifications 8 1 1 Outdoor Units 8...
Page 33: ...ESiEN09 06 A Function general Function 23 1 2 Operation Mode...
Page 58: ...Outline of Control ESiEN09 06 A 48 Function...
Page 71: ...ESiEN09 06 A Wiring Diagram of Control Box Control Box EKEQ CBV3 61 3 2 F box...
Page 109: ...Test Operation ESiEN09 06 A 100 Test Operation 1 2 2 Turn power on...