ESiEN09-06 A
Protection Control
Function
39
4.4
Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Tfin>84˚C
Fin temp. standby
Tfin<81˚C
INV upper limit rps = max
Under fin temperature
protection control
INV upper limit frequency: 1-step / 1 min up
from current compressor frequency Interval
Inverter fin temp.<81˚C continues
for 3 min. or more.
&
Tfin>84˚C
Tfin>93˚C
• When occurring 4 times within 60 min.,
the malfunction code “L4” is output.
Nomal operation
INV upper limit frequency: 1-step /
1 min down from current compressor
rps