ESiEN09-06 A
Other Control
Function
43
5.2
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting” or “Demand 2 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting” or
external input by external control adapter is required.
5.3
Heating Operation Prohibition
Heating operation is prohibited above 24°C ambient temperature.
Set item
Condition
Content
Demand 1
Mode 1
The compressor operates at approx. 60% or less of rating.
Mode 2
The compressor operates at approx. 70% or less of rating.
Mode 3
The compressor operates at approx. 80% or less of rating.
Demand 2
The compressor operates at approx. 40% or less of rating.