![background image](http://html.mh-extra.com/html/daikin/2amx40g2v1b/2amx40g2v1b_service-manual_501057269.webp)
SiBE12-933_A
Field Settings
Trial Operation and Field Settings
259
4.2
Indoor Unit - FFQ Series
4.2.1 How to Change the Field Settings with the Wired Remote Controller
Installation
conditions
The field settings have to be changed with the remote controller according to the installation
conditions.
Wired remote
controller
BRC1C61
To set the field settings, you have to change:
“Mode No.”
“First code No.”
“Second code No.”.
To change the field settings, proceed as follows:
Step
Action
1
Press the [Inspection / Test] button for 4 seconds during normal mode to enter the
field setting mode.
2
Press the [Temperature Adjust] button to select the desired “Mode No.”.
3
If the indoor unit is under group control, all settings for all the indoor units are
set at the same time. Use the codes 10 to 15 to apply this group control and
proceed to the next step.
If you want to set the indoor units of one group individually or if you want to
read out the last settings, use the codes 20 to 25 which are displayed in
brackets. Press the [Timer Selection] button to select the “Indoor unit No.” for
which you want to adjust the field settings.
4
Press the upper part of the [Clock] button to select the “First code No.”.
5
Press the lower part of the [Clock] button to select the “Second code No.”.
6
Press the [Reserve] button to confirm the setting.
7
Press the [Inspection / Test] button to return to normal mode.
SETTING
Mode No.
Indoor unit No.
(4)
(3)
(6)
(5)
(2)
(1) (7)
UNIT No.
(R11736)
Second
code No.
First
code No.
Field
setting
mode