SiBE12-933_A
Main Functions
Function and Control
65
1.8
Thermostat Control
Thermostat control is based on the difference between the room temperature and the set point.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
Heating
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
(R4668)
Room temperature – set point
Cooling : – 0.5°C
Dry : – 0.5°C
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
ON
OFF
C
B
A
(R6032)
Room temperature – set point
C
B
A
ON
Cooling : – 1.0°C
Dry : – 1.0°C
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
– 1.5°C
OFF
(R9686)
Room temperature – set point
A
OFF
OFF
ON
2.0°C
0.5°C
B
C
(R6033)
Room temperature – set point
1.0°C
A
B
C
OFF
ON
1.5°C
0.5°C