Main Functions
SiBE12-933_A
66
Function and Control
1.9
Night Set Mode
When the OFF timer is set, the NIGHT SET Mode is automatically activated. The NIGHT SET
Mode keeps the airflow rate setting.
The Night Set
Circuit
The NIGHT SET Mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers it slightly in
the case of heating. This prevents excessive cooling in summer and excessive heating in winter
to ensure comfortable sleeping conditions, and also conserves electricity.
Cooling
Operation
Wall Mounted Type, Floor Standing Type
Duct Connected Type, Floor / Ceiling Suspended Dual Type
Heating
Operation
0.5°C
1 hour
Timer operation
Night Set Circuit ON
+0.5ºC
temperature shift
Temperature
s0.5ºC
Temperature
setting
Operation stops
at the set hours
0.5°C
0.5°C
1 hour
Timer operation
Night Set Circuit ON
+0.5ºC
temperature shift
Operation stops
at the set hours
Temperature
s1ºC
Temperature
s0.5ºC
Temperature
setting
30 minutes
(A)
(B)
(B)
+0.5ºC temperature shift
Temperature setting remains the same
(A)
(B)
When outside temperature is normal and
room temperature is at set temperature.
When outside temperature is high (27ºC or higher).
(A)
Timer operation
Night Set Circuit ON
1 hour later
Thermostat
setting
2°C