Trial Operation
SiBE12-933_A
254
Trial Operation and Field Settings
3.2
Indoor Unit - FFQ Series
3.2.1 Checkpoints for Trial Operation
To carry out a trial operation, check the following:
Check that the temperature setting of the remote controller is at the lowest level in cooling
mode or use trial operation mode.
Go through the following checklist:
3.2.2 Trial operation
1. Open the gas stop valve.
2. Open the liquid stop valve.
3. Electrify for 6 hours.
4. Set to cooling operation with the remote controller and start operation by pressing [ON/OFF]
button (
).
5. Press the [Inspection / Test] button (
) 4 times (2 times for wireless remote controller) and
operate at trial operation mode for 3 minutes.
6. Press the [Airflow Direction Adjust] button (
) to make sure the unit is in operation.
7. Press the [Inspection / Test] button (
) and operate normally.
8. Confirm all the function of unit according to the operation manual.
9. If the decoration panel has not been installed, turn off the power after the trial operation.
Checkpoints
Cautions or warnings
Are all units securely installed?
z
Dangerous for turning over during storm
z
Possible damage to pipe connections
Is the earth wire installed according to the applicable
local standard?
Dangerous if electric leakage occurs.
Are all air inlets and outlets of the indoor and outdoor
units unobstructed?
z
Poor cooling
z
Poor heating
Does the drain flow out smoothly?
Water leakage
Is piping adequately heat-insulated?
Water leakage
Have the connections been checked for refrigerant
leakage?
z
Poor cooling
z
Poor heating
z
Stop
Is the supply voltage conform to the specifications on the
name plate?
Incorrect operation
Are the cable sizes as specified and according to local
regulations?
Damage of cables
Are the remote controller signals received by the unit?
No operation