SiBE12-933_A
Main Functions
Function and Control
73
1.14 Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed / setting
temperature is converted to the following states in a period of 20 minutes.
In case of F(A)TXS20-50G
Ex.) : POWERFUL operation in cooling mode.
Refer to “Fan Speed Control” on page 61 for detail.
Operation mode
Fan speed
Target set temperature
COOL
H tap + 50 rpm
18°C
DRY
Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
HEAT
H tap + 50 rpm
30°C
FAN
H tap + 50 rpm
—
AUTO
Same as cooling /
heating in POWERFUL
operation
The target is kept
unchanged
(R4560)
Target temp.
Set temp.
18°C
POWERFUL ON
POWERFUL OFF
Fan
H tap
Set tap
50rpm
20min.
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. POWERFUL operation is OFF.