Field Settings
SiBE12-933_A
256
Trial Operation and Field Settings
G-Series
< Floor Standing Type>
1) Remove the front grille.
2) Lift the sensor PCB fixing plate and remove the front shield plate.
3) Disconnect the connectors [S1] [S41] [S42].
4) Remove the electric box (1 screw).
5) Pull out the indoor heat exchanger thermistor.
6) Remove the shield plate (8 tabs).
7) Cut the address jumper JA on the indoor unit PCB.
8) Cut the address jumper J4 in the remote controller.
(Refer to “Wireless remote controller”.)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
(R12216)
3) Connector [S42]
3) Connector [S41]
3) Connector [S1]
4) Remove the screw.
5) Indoor heat exchanger
thermistor
JA
Address
EXIST
1
CUT
2
JA
JC
JB
2) Front shield plate
6) Shield plate
2) Sensor
PCB fixing
plate
(R11692)