SiBE12-933_A
Forced Cooling Operation Mode
Trial Operation and Field Settings
251
2. Forced Cooling Operation Mode
Outline
Forced operation mode includes only forced cooling.
Detail
ex.Wall mounted type G-series
Item
Forced Cooling
Conditions
The forced cooling operation is allowed when both the following conditions
are met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
Start
Press the forced cooling operation ON/OFF button (SW1 or S1W) on the
indoor unit for 5 seconds.
Operating room
All rooms
Command frequency
40 class: 70 Hz
50 class: 47 Hz
End
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1 or S1W) on the
indoor unit again.
Others
The protection functions are prior to all others in the forced cooling
operation.
(R12779)
ON/OFF button (SW1 or S1W)