116
3.
Use a No. 10 Hex wrench to remove the 4 screws between the
inverter and the wiring box. Lift the inverter enclosure and
disconnect from the wiring box.
Figure 7-4 Disconnect the main housing from the wiring box
4.
If the replacement inverter is onhand and to be installed
immediately, skip this step and refer to section 3.2 for installation
of the inverter. Otherwise, use a No. 2 Phillips head screwdriver
to remove the 2 screws on the left side of the wiring box, and
remove the bulkhead cover. Attach the cover on the connector of
wiring box. Torque value: 1.6N.m (14.2in-lbs)
Figure 7-5 Install the cover on the connector of the wiring box