98
MPPTScanPeriod (s)
MPPT Scan Cycle
(300,
3600
, 5400)
(300,
3600
, 5400)
Other Parameters (Cont’d)
IEEE1547
Rule21
Parameter name
Description
Setting Range
(Min,
Default
, Max)
Setting Range
(Min,
Default
, Max)
ISOProtection
(Ω)
Minimum
insulation
resistance
(1k,
140k
, 2000k)
(1k,
140k
, 2000k)
StarUPMinTemp (C)
The minimum
startup
temperature
(-35,
-30
, -20)
(-35,
-30
, -20)
DuplicationGroup
Parameter of
repetitive control
{0,
0
, 100}
{0,
0
, 100}
CtrParaGroup
The enabled
control parameters
group.
{0,
4
, 4}
{0,
4
, 4}
PID Check Setting
PID Checking
enable/disable
control
{0,
0
, 1}
{0,
0
, 1}
Island Protect
Island
enable/disable
control
0: Disable
1: Enable
{0,
1
, 1}
{0,
1
, 1}
Fan Detect
Fan detection
enable/disable
control
0: Disable
1: Enable
{0,
1
, 1}
{0,
1
, 1}
4.4.2.9 File Export (local)
File Export is used to export the data including
Running History
and
Fault Record
to a flashdrive. Press
ENT
and use
UP
and
DOWN
arrows
to export the data, and press
ENT
to confirm the setting.
4.4.2.10 Firmware update (local)
Firmware update is to update the versions of firmware including
LCD
Firmware
and
DPS Firmware
. Press
ENT
and use
UP
and
DOWN
arrows to update the data, and press
ENT
to confirm the setting. For
remote Firmware updating see Section 6.5.
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...