20
300mm
(11.8in.)
300mm
(11.8in.)
500mm
(19.7in.)
=600mm
(23.6in.)
BAFFLE
BAFFLE MUST:
1. EXTEND MIN. ABOVE AND BELOW FANS
2. EXTEND 4" MIN. PAST FRONT OF INVERTER
3. LOCATED 8" MIN. FROM BOTH INVERTERS
Figure 3-3 Inverter Wall Mounting Dimensions
INSTRUCTION:
If the inverter is installed on Unistrut or the array racking (instead of
solid wall), the space from the bottom of one inverter to the top of the
inverter below may be as small as 3.9in (100mm). The spacing below
may be as small as 11.8in (300mm).