88
Table 4-5 HVRT Parameters (IEEE5147 and Rule21)
HVRT
IEEE1547
Rule21
Parameter name
Description
Setting Range
(Min,
Default
, Max)
Setting Range
(Min,
Default
, Max)
HVRTVolt (1,2)
Threshold value of high
voltage ride through (1
st
& 2
nd
point)
{100%,
125%
, 135%}
{100%,
125%
, 135%}
{100%,
125%
, 135%}
{100%,
125%
, 135%}
HVRTTime (1,2)
Time of Level high voltage
ride through (1
st
& 2
nd
point)
{0,
0
, 655}
{0,
0.8
, 655}
{0,
0
, 655}
{0,
0.11
, 655}
HVRTVolt (3,4)
Threshold value of high
voltage ride through (3
rd
& 4
th
point)
{100%,
124%
, 135%}
{100%,
124%
, 135%}
{100%,
120%
, 135%}
{100%,
120%
, 135%}
HVRTTime (3,4)
Time of Level high voltage
ride through (3
rd
& 4
th
point)
{0,
0.8
, 655}
{0,
12.5
, 655}
{0,
0.11
, 655}
{0,
12.5
, 655}
HVRTVolt (5,6)
Threshold value of high
voltage ride through (5
th
& 6
th
point)
{100%,
115%
, 135%}
{100%,
115%
, 135%}
{100%,
110%
, 135%}
{100%,
110%
, 135%}
HVRTTime (5,6)
Time of Level high voltage
ride through (5
th
& 6
th
point)
{0,
12.5
, 655}
{0,
12.5
, 655}
{0,
12.5
, 655}
{0,
12.5
, 655}
HVRTVolt (7,8)
Threshold value of high
voltage ride through (7
th
& 8
th
point)
{100%,
115%
, 135%}
{100%,
115%
, 135%}
{100%,
110%
, 135%}
{100%,
110%
, 135%}
HVRTTime (7,8)
Time of Level high voltage
ride through (7
th
& 8
th
point)
{0,
12.5
, 655}
{0,
12.5
, 655}
{0,
12.5
, 655}
{0,
12.5
, 655}
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...