95
Table 4-9 lists the parameters for PF Set, PF(P) Curve and Q(U)
Curve modes. Press
ENT
to start the modes after the parameters
are set.
Table 4-9 Reactive Power Control (IEEE-1547 and Rule21)
Grid Reactive Power Derating
IEEE1547
Rule21
Parameter name
Description
Setting Range
(Min,
Default
, Max)
Setting Range
(Min,
Default
, Max)
QuCurveU1 (V)
Voltage of Q(U) Curve
point 1
{100%,
107.99%
,
110%}
{100%,
107.99%
,
110%}
QuCurveQ1 (%)
Reactive power of Q(U)
Curve point 1
{-66%,
0
, 66%}
{-60%,
0
, 60%}
QuCurveU2 (V)
Voltage of Q(U) Curve
point 2
{108%,
110%
,
110%}
{108%,
108%
,
110%}
QuCurveQ2 (%)
Reactive power of Q(U)
Curve point 2
{-66%,
-50%
, 66%}
{-60%,
-60%
, 60%}
QuCurveU1i (V)
Voltage of Q(U) Curve
point 1i
{90%,
92.01%
, 99%}
{90%,
99%
,
99%}
QuCurveQ1i (%)
Reactive power of Q(U)
Curve point 1i
{-66%,
0
, 66%}
{-60%,
0
, 60%}
QuCurveU2i (V)
Voltage of Q(U)Curve
point 2i
{80%,
90%
, 92%}
{80%,
92%
, 92%}
QuCurveQ2i (%)
Reactive power of
Q(U)Curve point 2i
{-66%,
50%
, 66%}
{-60%,
60%
, 60%}
QuCurveTriPower (V)
The trigger voltage of
Q(U)Curve
{5%,
20%
, 100%}
{5%,
20%
, 100%}
QuCurveUndoPower
(V)
The end voltage of
Q(U)Curve
{5%,
5%
, 100%}
{5%,
5%
, 100%}
CtrMode
The control mode of
reactive power
0: Disable dispatch
mode.
1: Remote dispatch
mode.
2: Local control, by Q
3: Local control, by PF
4: PF(P) curve
5: Q(U) curve
{0,
0
, 5}
{0,
0
, 5}
Percentage
Local Power Factor
Setting
{-66%,
0%
, 66%}
{-60%,
0%
, 60%}
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...