38
Table 3-4a DC Input Specifications (Independent Mode)
When the input power for one MPPT zone exceeds the maximum allowable,
but the combined input power is still below the inverter input specifications the
inverter must be set in
Parallel Mode
(1 MPPT). In this mode, all strings should
contain the same number of modules, be of the same manufacturer, orientation
and tilt.
Table 3-4b DC Input Specifications (Parallel Mode)
Specification
(Independent Mode - per MPPT)
Model
SCA50KTL-DO/US-480
SCA60KTL-DO/US-480
Max PV Power
30kW (Combined ≤ 75kW)
33kW
(Combined ≤ 90kW)
Max PV Voltage
1000Vdc
1000Vdc
Start-up
Voltage / Power
330 / 80W
330 / 80W
Operating Voltage
200-950Vdc
200-950Vdc
MPPT Voltage
Range
480-850Vdc
540-850Vdc
Maximum PV
Current (Isc x
1.25)
68A
68A
Specification
(Parallel Mode - 3 MPPTs combined)
Model
SCA50KTL-DO/US-480
SCA60KTL-DO/US-480
Max PV Power
75kW
90kW
Max PV Voltage
1000Vdc
1000Vdc
Start-up
Voltage / Power
330 / 80W
330 / 80W
Operating Voltage
200-950Vdc
200-950Vdc
MPPT Voltage
Range
480-850Vdc
540-850Vdc
Maximum PV
Current (Isc x 1.25)
204A
204A
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...