Table 3-10 Torque and Conductor Specifications
Connection Point
Conductor Range
Torque Value
AC output terminal block
6-3/0 AWG (CU/AL)
14.25 N-m (126 in-lbs
)
Internal grounding bar
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
External grounding point
6-4 AWG (CU)
5.65 N-m
(
50 in-lbs
)
The maximum acceptable conductor size that may be terminated to the AC output
terminal is restricted based on the compression lug maximum dimensions shown in
Figure 3-34
.
Standard 1-hole Lug
Metric 1-hole Lug
Figure 3-34 Compression Lug (OT Terminal) maximum dimensions