137
Pin/Pn
3000 4000
Altitude(m)
100%
70%
-30%/km
Figure 10-3 SCA50/60KTL Derating Curve with High Altitude
10.3.4 Grid Voltage Derating Graph
When the grid voltage is within 100%~110% (Un ~ 1.1*Un) of the Rated
Output Voltage, the inverter output power (Pn) may reach 100%. When
the grid voltage is lower than the Rated Output Voltage, the inverter will
limit the AC Output Current and the output power (Pn) will begin to
derate, as shown in Figure 10-4.
20%
40%
60%
80%
100%
Po/Pn
0.88*Un Un 1.1*Un
Grid Voltage (Vac)
Figure 10-4 SCA50/60KTL Derating Curve of Grid Voltage