81
4.4.2.3 Protect Parameters
This interface is used to display and set the Protect parameters of the AC
grid voltage, frequency and recovery, etc, as shown in Figure 4-13.
Voltage Moving Average
P6/7
MaxTripT(S)
VolMax
MinTripT(S)
VolMin
600.00
88.00%
600.00
110.00%
Grid Over Voltage Protection
VolMaxTripT1(S)
GridVolMax1
P1/7
VolMaxTripT2(S)
GridVolMax2
VolMaxTripT3(S)
GridVolMax3
0.16
120.00%
1.00
110.00%
0.16
120.00%
Grid Under Voltage Protection
P2/7
VolMinTripT1(S)
GridVolMin1
VolMinTripT2(S)
GridVolMin2
VolMinTripT3(S)
GridVolMin3
1.00
60.00%
2.00
88.00%
0.16
45.00%
Grid Under Frequency Protection
P4/7
FrqMinTripT1(S)
GridFrqMin1(Hz)
GridMinTripT2(S)
GridFrqMin2(Hz)
FrqMinTripT3(S)
GridFrqMin3(Hz)
0.16
57.0
2.00
59.5
0.16
57.0
Grid Recovery
P5/7
VolMin
VolMax
FrqMax(Hz)
VolRecoveryT(S)
FrqRecoveryT(S)
FrqMin(Hz)
60.3
300.00
90.00%
107.92%
300.00
59.8
Enable
Disable
Disable
Grid Voltage Balance
P7/7
GridVolBalance
10.00%
Disable
Enable
Disable
Enable
Enable
Enable
Grid Over Frequency Protection
P3/7
FrqMaxTripT1(S)
GridFrqMax1(Hz)
GridMaxTripT2(S)
GridFrqMax2(Hz)
FrqMaxTripT3(S)
GridFrqMax3(Hz)
0.16
62
2.00
60.5
0.16
Enable
Enable
Disable
Disable
Enable
Enable
62
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
Figure 4-13 Protection Parameter Settings
There are 7 pages of parameters displayed. Navigate the parameters by
pressing
and
. Then press
ENT
to access the highlighted
selection. Change the parameter value by pressing
and
then
ENT
to confirm the parameter setting. The LCD will display new
parameters if the setting is successful, otherwise the old parameters will
remain displayed on the LCD.
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...