Ref.no.: 003274/Revision 2.4 @2019 Control Data Systems Page 44
|
201
Monitoring Host
page. Use the information under
Help
in both pages for guidance. Back in the
Modbus fields, each line inserted will be completed as follows:
a.
For each device, there will be as least as many lines in the
Input Registers
as there are
channels in
Monitoring Host
;
b.
Each line will contain 9 values, separated by commas without spaces in between:
-
start_address: represents the register address where the data will start to appear;
-
word_count: represents the number of registers held for that particular line (in this
case 3: first will represent the status of the data, the next two are hexadecimal
values, composing the actual data from the sensor);
-
EUI64: the device EUI, without the colons character (:);
-
The values for TSAPID, ObjId, AttrId, Idx1 and Idx2 are found in the
Monitoring Host
channel lines of the device;
-
MethId: will be 0;
-
Status_byte: will be 2.
Figure 5.4.8 Monitoring Host Help Information
Figure 5.4.9 Modbus Help Information
c.
After each completed line, press
Save
;
d.
Press
Activate
after all the lines have been inserted.
7.
The Modbus values can be read using a Modbus client (recommended ModbusMaster from
Farrellton Solar).