Ref.no.: 003274/Revision 2.4 @2019 Control Data Systems Page 21
|
201
5
Quick Start Network Configuration
The aim of this section is to guide the user through a simple and rapid process of configuring the VR950
Gateway, for either ISA100.11a or WirelessHART, and to provision a device to send data and to read it
using the Gateway web interface (Monitoring Control System) as well as Modbus TCP/IP external client.
5.1
VR950 Configuration
5.1.1
Powering the VR950 Gateway
The VR950 Gateway module is powered using a 24V, 1A Terminal Block power supply connector.
The
ETH1 connector
is used for network connection. The static default IP address is 192.168.0.101. The
VR950 boards can obtain also a dynamic IP address is a DHCP server is active in the network.
The redundancy setup comprises two VR950 modules interconnected via a straight Ethernet cable using
the
ETH2 connector
.
5.1.2
IP configuration
A new static IP address will be set using the admin web interface accessible at the following address:
192.168.0.101/admin/login.html
. The default credentials are:
-
Username: admin
-
Password: adminadmin
The static IP configuration is available in the website Configuration section under the Network tab as
seen below:
Figure 5.1.1 Default admin website static IP configuration
After changing the IP, press the
Hard Restart
button underneath to reboot the VR950 and activate the
new settings.