Ref.no.: 003274/Revision 2.4 @2019 Control Data Systems Page 30
|
201
5.3
Configuring a CDS VS210 for WirelessHart
Figure 5.3.1 VS210 scheme
In order to setup a VS210 to join a WirelessHART network, the following changes steps must be taken
(see
Figure 5.3.1
):
1.
Remove jumper from
JP203
;
2.
Remove jumper from
JP501
;
3.
Switch
S202.1
will be set to
ON
and
S202.2
will be set to
OFF
;
4.
Power must be supplied through the USB or J101;
5.
If the device was previously configured for either ISA100.11a or WirelessHART, a reset from the
Reset application
button.
The software used for provisioning the Emerson WirelessHART device is the
WirelessHART Provisioning
Tool
. Since the tool used for provisioning is a
USB MicroLink Hart Protocol Modem
provisioning, a
software for it will also be required.
1.
Go to Windows Start and open “Device Manager”. Roll down the options under “Ports (COM &
LPT)”.
2.
Plug the MicroLink Modem into an USB port. The Modem’s name should now appear under
“Ports” in the Device Manager.