ID-Mobile Global Guide
183
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
22
Description
Closed output opens the fuel solenoid. Adjustable to DIESEL or GAS.
Fuel Solenoid
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
1
Description
Binary output for Horn, Buzzer alarm acoustic indication. Output is automatically switched off after
. Horn is active unlimited time (until until Horn reset or Fault reset is pressed / activated)
when Horn timeout = 0.
Horn
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
284
Description
Output is closed for 1 sec when Horn reset button (e.g. from DriveMonitor is activated).
HrnResButtEcho
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
39
Description
The output closes during engine start, after Idle time setpoint elapses. The output opens again after Cooling
time is finished. The opposite logic output Nominal/Idle is available as well.
Note:
Connect Binary output IDLE / NOMINAL to electronic speed governor to switch the speed:
opened = IDLE, closed=RATED.
Idle/Nominal
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
37
Description
Ignition system activation / deactivation during start stop procedure.
Ignition