ID-Mobile Global Guide
82
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
1 .. 4000 [min]
Default value
1
Step
1 min
Comm object
8781
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Time interval between prelubrication cycles.
Note:
To use Prelubrication, configure Binary output PRELUBRICATION at first.
Prelubrication is disabled in controller OFF mode or when is Prelubr time set to zero.
When engine is running PRELUBRICATION binary output is opened.
Prelubrication starts Prelubr Pause after engine goes to stop. Prelubrication starts immediately when:
- Controller power supply turns on
- mode changes from OFF to another
- Emergency stop is released.
Controller indicates Not ready state during this the first prelubrication period.
Prelubr Pause
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 600 [s]
Default value
60
Step
1 s
Comm object
9815
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Under normal conditions the engine must certainly stop within this period.
Stop Time = STOP
press
→ Cooling Time → Stop valve
Stop Time