ID-Mobile Global Guide
158
LBI: N
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
41
Description
Skips Idle time and switch controller from Idle to running state when closed before Idle time is over.
Nominal Speed
LBI: P
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
173
Description
Prestart override activation skips the Prestart procedure (can be adjusted up to 600 sec).
Skip Prestart is possible by binary or by repeated press of START button.
Example: Finish engine preheating (prelubrication) based on temperature (pressure) limit..
PrestartOvrd
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
174
Description
Active input disables (switch off) corresponding PWM signal on selected Binary output BO9.
PWM9 DISABLE
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
175
Description
Active input disables (switch off) corresponding PWM signal on selected Binary output BO10.
PWM10 DISABLE
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
176
Description
Active input disables (switch off) corresponding PWM signal on selected Binary output BO11.
PWM11 DISABLE