ID-Mobile Global Guide
156
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
141
Description
Active input blocks ECU communication fail. Function can be used e.g. when ECU is switched off after
engine stop.
ECUComFailBlck
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
45
Description
Controller does not activate binary output Fuel solenoid when engine starter is activated externally.
Emerg. Manual
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
40
Description
Engine Shut down activation. It is recommended to configure Emergency stop as normally closed contact
from safety reason (this configuration is in default aid archive).
Emergency Stop
LBI: F
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
152
Description
Binary input for Alarm acknowledge (edge sensing) has the same function as controller front panel button
Fault reset.
Note:
There is separate acknowledge for ECU Alarms – see
.
Fault Reset
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
160
Description
Running Engine speed is set to
FireAlarmSpeed (AS only) (page 85)
if input is active.
Fire Speed (AS only)