ID-Mobile Global Guide
85
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0.0 .. 100.0 [%/s]
Default value
5
Step
0.1 %/s
Comm object
9984
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Speed ramp for BI Speed Up/Down not for Analog input request.
BI Speed Ramp
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 100 [%]
Default value
50
Step
1 % of Requested RPM range.
Comm object
10008
Related applications
Config level
Standard
Setpoint visibility
Always
Description
When Binary input Fire speed is closed the binary output Clutch connect opens and engine Requested RPM
is set to Engine params: FireAlarmSpeed value.
FireAlarmSpeed (AS only)
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
[ENABLED / DISABLED]
Default value
DISABLED
Step
Comm object
10098
Related applications
Config level
Standard
Setpoint visibility
Always
Description
ENABLED
Engine speed request is defined by Engine params: Local speed setpoint. The speed
request can be changed regardless on controller mode.
DISABLED
Requested speed is changed via Binary inputs Speed up, Speed down or via analog input
Requested RPM.
EnLocalSpeed