ID-Mobile Global Guide
185
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
17
Description
The output is closed in controller OFF mode.
OFF Mode
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
61
Description
Output closes with binary output Prestart and opens with binary output Cooling pump.
Operational
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
49
Description
Periodic prelubrication function – see
and
.
Prelubrication
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
36
Description
The output closes prior to the engine start (Preheat, Prelubrication) for
Prestart
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
280
Description
Output is closed when engine is ready for remote start.
RdyForRemStart
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
67
Description
Output closes if the engine is in Running state and can be loaded. Opens in Cooling state. Active only if
RPM >
Ready To Load