ID-Mobile Global Guide
81
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1 s
Comm object
9097
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Idle time delay starts when RPM exceeds Start RPM.
During the Idle time is Binary output IDLE/NOMINAL opened and after then is closed. Binary output
IDLE/NOMINAL opens after Cooling period is over.
Idle Time
Setpoint group
Engine parameters
Related FW
2.6.0
Range [units]
0 .. 600 [s]
Default value
0
Step
1 s
Comm object
8780
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This is the time the binary output PRELUBRICATION is active. The controller will activate binary output
PRELUBRICATION for this amount of time, then pause for Prelubr pause, then activate again. This will
continue the entire time the engine is not running. Function is not active in controller OFF mode.
Prelubr Time