ID-Mobile Global Guide
170
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
359
Description
Indication of Binary output 15 and/or Binary output 16 fail.
Note:
Possible Binary outs fails:
Short circuit (over 8 Amps) between BOUT 1-2; BOUT 3-4; BOUT 5-6; BOUT 7-8; BOUT 9-10; BOUT
11-12; BOUT 13-14; BOUT 15-16;
Short circuit (over 8 Amps) of any BOUT9-16 to BAT MINUS
Short circuit (over 8 Amps) of any BOUT9-16 to BAT PLUS
Overheat (over 150 °C on chip) and Undervoltage below 5.3 V of chip supply.
BO 15/16 Fail
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
265
Description
Output is closed/opened with rising edge of Binary input Rem On/Off when engine is in Running state and
engine RPM is over
Output opens when RPM is below
. Close load can be opened remotely (e.g. from
DriveMonitor) when Binary input Remote On/Off is closed.
Close Load
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
285
Description
Output is closed for 1 sec when Clutch button (e.g. from DriveMonitor is activated).
ClutchButtEcho
Related FW
2.6.0
Related applications
AMF, MRS
Comm object
269
Description
Output is closed when any analog extension (IS-AIN, IGS-PTM) unit does not communicate.
Comm AIN fail