ID-FLX Lite Global Guide
75
6 Troubleshooting
6.3 Diagnostic messages read from ECU
6.1 Alarm management
Following alarms are available:
Sensor fail
Warning
Cooldown
Shut down
Note:
Type of protection for binary and analog inputs is adjustable in PC tool LiteEdit. In window Modify after
double click on input adjust Alarm type.
6.1.1 Sensor fail (Fls)
Sensor fail is detected when measured value is 6 % out of selected sensor characteristic. Sensor fail is
indicated by ##### symbol instead of measured value.
6.1.2 Warning (Wrn)
When warning comes up, only alarm outputs and common warning output are closed.
Note:
For list of possible warning alarms
see List of possible alarms on page 76
6.1.3 Cooldown (Cd)
When cooldown comes up, engine is stoped slowly over cooling state.