ID-FLX Lite Global Guide
103
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[OFF, MAN, AUT]
Default value
-
Step
-
Comm object
8315
Related applications
Description
Equivalent to Controller mode changes by MODE→ or ←MODE buttons.
Note:
Controller Mode change can be separately password protected.
ControllerMode
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[ENABLED, DISABLED]
Default value
-
Step
-
Comm object
9983
Related applications
Description
DISABLED
Controller stays in AUT mode after Fault reset. Default state.
ENABLED
Automatic switch from AUT to MAN mode after Fault reset to avoid automatic engine start.
This function is active for Shut down protection only.
FltResGoToMAN
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
0 .. 60 [min]
Default value
0 … means that the
display lights all the
time
-
Step
1 [min]
Comm object
10121
Related applications
Description
The display backlight is switched off after timeout.
DispBacklightTO
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
[Nom/Idle, N/I Init, Conveyor, RegReqst, R RegDis, CloseLoad, Toggle]
Default value
-
Step
-
Panel Button
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...