ID-FLX Lite Global Guide
124
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
..
[RPM]
Default value
1200
-
Step
1
Comm object
10096
Related applications
Description
The setpoint presets the minimum engine speed in the “Running” operation state. Also see other conditions
in the chapter below.
Note:
See
MinSpeedLim
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
.. 4000 [RPM]
Default value
2700
-
Step
1
Comm object
10097
Related applications
Description
The setpoint presets the maximum engine speed in the “Running” operation state. Also see other conditions
in the chapter below.
Note:
See
MaxSpeedLim
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
..
[RPM]
Default value
1250
-
Step
1
Comm object
10099
Related applications
Description
The setpoint presets the required engine speed during the ‘Speed Sel 1’ binary input is active. Function
depends on RetToSpeedAdj setting.
Note:
See
BI Speed Sel 1