ID-FLX Lite Global Guide
66
LAO
Function
LoadLimitAOut
Analog output of Load Limitation PI control loop.
Functions 1 and 2 setpoints
Load limit
Values
Load Input
ECU: RPM, Load,
CU: AI1-AI9,
AIO: AI1-AI4
Load Bias
0 - 10000 [ - ]
LoadRequest 1
±10000 [ - ]
LoadRequest 2
±10000 [ - ]
LoadReq Ramp
1 - 10000 [ - ]
LoadUpLimit
0 - 10000 [ - ]
LoadDnLimit
0 - 10000 [ - ]
Load Gain
0.0 ±200.0%
Load Integral
0.0 % - 100.0 %
Load CMP Input
ECU: RPM, Load,
CU: AI1-AI9,
AIO: AI1-AI4
Load CMP Off
±10000 [ - ]
Load CMP On
±10000 [ - ]
Note:
For more information
Functions 1 and 2 examples
General PI control loop
Engine Load limitation with analog output
General comparator
Engine Load limitation with On/Off output
Speed switch
General PI control loop
Purpose: PI control of any value.
Description: PI detects the difference between actual and requested value and changes the output to keep the
controlled value on the limit. Can be used PI in function 1 or 3
Function requires plug-in module with Analog output.