ID-FLX Lite Global Guide
88
ECU shall show ####, but no alarm is displayed. The output ECU CommOK follows the real situation that
means it is not active anytime when the ECU does not communicate.
The
closes at the beginning of prestart and opens if the engine shall be stopped.
The engine is started via standard contact output or via CAN bus.
Value name
Short name
Dimension
Type
Frame name
EngOil Filter Diff.Press
OilDiffPres
bar
ANA
DD
Amber Warning Lamp
AmberWrnLamp
-
BIN
DM1
Malfunction Lamp
MalfunctLamp
-
BIN
DM1
Protect Lamp
ProtectLamp
-
BIN
DM1
Red Stop Lamp
RedStopLamp
-
BIN
DM1
Engine speed
RPM
RPM
ANA
EEC1
Engine Oil Pressure
EngOil Press
bar
ANA
EFLP1
Coolant Temp
Coolant Temp
°C
ANA
AT1
Total Engine Hours
EngineHours
h
ANA
HR
Boost Pressure
Boost Press
bar
ANA
IC
Intake Manifold Temp
Intake Temp
°C
ANA
IC
Practical examples of values read from ECU
If Cummins-Modbus x.x option is selected, following values are read from Modbus Register Data (for QSX15,
QSK45, QSK60):
Value name
Short name
Dimension
Type
Frame name
Red Shutdown Lamp
Red Lamp
-
BIN
10005
Yellow Warning Lamp
Yellow Lamp
-
BIN
10006
Engine Speed
RPM
RPM
ANA
30001
Coolant Temp
Coolant Temp
°C
ANA
30002
Oil Pressure (psig)
Oil Press
bar
ANA
30003
Oil Pressure (psia)
Oil Press
bar
ANA
30003
Running Time
Running Time
h
ANA
30008
Fuel Rate (UK)
Fuel
L/h
ANA
30018
Fuel Rate (US)
Fuel
L/h
ANA
30018
Intake Manifold Press
Intake Press
bar
ANA
30530
Intake Manifold Temp
Intake Temp
°C
ANA
30531
8.6 ECU Analog inputs
Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes, e.g.
measuring, displaying and alarm activation related to various quantities. The configuration thus allows using
nine analog inputs on the central unit and four analog inputs on plug-in module if connected.
If the engine without ECU is controlled by ID-Lite, the first analog input is permanently configured to Oil
Pressure, other analog inputs remain freely configurable.
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...