ID-FLX Lite Global Guide
141
Comm object
8260
Related applications
Description
Limit for Warning Underspeed protection. Active protection is indicated as “Wrn Underspeed” in Alarm list.
Under speed Warning protection is inactive 5 s after RPM is over
and during the
Idle time.
The
is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
5
-
Step
1
Comm object
12620
Related applications
Description
Engine is switched to Cooling state when Binary input FlowSwitch is not closed within Flow SwitchDel after
„Running“ (Ready to load) engine state activation.
Flow SwitchDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
DISABLED, ENABLED [-]
Default value
-
Step
-
UnderspeedSd
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...