ID-FLX Lite Global Guide
206
Related FW
2.5.0
Related applications
Comm object
1296
Description
Output closes if the engine “Sd Underspeed” alarm activates i.e. when RPM is below the
limit.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Underspeed
Related FW
2.5.0
Related applications
Comm object
1291
Description
Output closes after the engine start-up fails.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Start failed
Related FW
2.5.0
Related applications
Comm object
1292
Description
Output closes when ID-Lite performs reset during start procedure (probably due to weak battery).
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Battery flat
Related FW
2.5.0
Related applications
Comm object
928
Description
Output closes when battery over/under voltage warning appears.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
V batt failed