Cisco TelePresence System TX9000 and TX9200 Assembly, Use & Care, and Field-Replaceable Unit Guide
OL-27038-01
Chapter 2 Room Requirements for the TX9000 and TX9200 Systems
Room Dimensions for the TX9000 and TX9200
Figure 2-1
TX9000 Minimum Room Dimensions
343555
1
2
6
4
3
8
7
5
Table 2-4
Callouts for
Callout
Description
1
The minimum room width is 19’ (5800 mm). Rooms can be wider.
2
The minimum room depth is 14’4” (4370 mm) for systems that use a wall-mounted reflector wall, and
15’ (4570 mm) for systems that use a free-standing reflector wall. Rooms can be deeper.
3
Systems that use a free-standing reflector wall only:
The minimum distance between the rear edge
of the free-standing reflector wall and the wall of the room is 5” (127 mm). The wall depth is 3” (76
mm).
Note
The minimum distance between the front of the free-standing reflector wall and the wall of the
room is 8” (203 mm).
4
The distance between the light reflector and the table edge of the TX9000 is 10’ 3” (3124 mm).
5
The minimum space between rear edge of the table and the rear wall is 44” (1120 mm).
6
The width of the TX9000 light reflector is 18’ 9” (5715 mm).
7
The distance between the camera and the table edge at the outer chair position is 8.3’ (2510 mm).
8
Systems that use a wall-mounted reflector wall only:
The minimum distance between the rear of the
system and the front of the wall-mounted reflector wall is 13.7 inches (348 mm).