2-2
Cisco TelePresence System TX9000 and TX9200 Assembly, Use & Care, and Field-Replaceable Unit Guide
OL-27038-01
Chapter 2 Room Requirements for the TX9000 and TX9200 Systems
Summary of Room Requirements For the TX9200
Summary of Room Requirements For the TX9200
summarizes the room requirements for the TX9200:
Table 2-1
Summary of Room Requirements for the TX9000
Minimum Room Size
Width / Depth / Height
19’ x 14’4” x 8’ (5800 mm x 4370 mm x 2440 mm)
Note
The dimensions provided are for a system that uses a wall-mounted
reflector wall. For systems that use a free-standing reflector wall,
increase the minimum depth from 14’4” (4370 mm) to 15’ (4570
mm)
Lighting
200(minimum)-400(recommended) lux facial light (vertical plane)
Shoulder Light: No more than twice the facial light (measured on the
horizontal plane)
Note
This is lighting for 30 frames per second (FPS) conferences. 60
FPS conferences may require additional lighting.
Acoustics
Ambient Noise
For non-critical voice frequencies:
•
150-700 for non-critical voice frequencies (>500 Hz, or <2 kHz)
•
150-500 for critical voice frequencies (500 Hz-2 kHz)
•
45dBA SPL
•
NC30
Reverberation: 150-700ms
Acoustic panels on side walls are optional, but can be used to remedy
acoustic deficiencies.
Power
2.93 kW required
Participant convenience ports consume additional power (maximum of
1.44 kW for six particpants)
HVAC
Independent Room Control
Typical Cooling 9,500 BTU/Hr
Design
Aesthetic Continuity highly desirable
For best video quality:
•
Avoid high contrast elements such as very dark or bright colors
•
Avoid glossy finishes
•
Avoid clutter
For more information, refer to the
Cisco TelePresence Wall Color Guide
at
the following URL: