Chapter 2 Room Requirements for the TX9000 and TX9200 Systems
Power Requirements For the TX9000 and TX9200
The TelePresence TX9000 and TX9200 use Power Distribution Units (PDUs) to connect the components
to the power circuits. See
for the wattage that is required for each PDU.
Note
US electrical code requires a maximum of 16 amps on a 20 amp circuit.
Table 2-14
Components and Total Power Usage in Watts per Power Distribution Unit (PDU)
PDU
Components
PDU 1
Power supply for LCU (1 of 2)
Codec TS2
Left display
Total watts: 837.6
PDU 2
Power supply for LCU (2 of 2)
Codec TS1
Audio/video extension unit
Presentation display
Camera processor module
Total watts: 630
PDU 3
Codec TS3
Right display
Total watts: 729.6
PDU 4
Codec TS4
Center display
Total watts: 729.6
Table 2-15
Components and Total Power Usage in Watts per Power Distribution Unit (PDU) for
First and Second Row Conference Participants (Optional)
PDU
Components
PDU 5
Power supply for front row/first row conference participants (TX9000 and TX9200
systems)
Total watts: 1440