Cisco TelePresence System TX9000 and TX9200 Assembly, Use & Care, and Field-Replaceable Unit Guide
OL-27038-01
Chapter 2 Room Requirements for the TX9000 and TX9200 Systems
Summary of Room Requirements For the TX9200
Note
These dimensions are for the full, 18-seat version of the TX9200. A 10- and 14-seat version is also
offered. For dimensions for these systems, see
Chapter 13, “Building the Second Row Table For a 14-
The following sections elaborate on each requirement.
Table 2-2
Summary of Room Requirements for TX9200
Room
Size
Minimum
Width / Depth / Height
31’ x 21’ 5” x 8' (9450 mm x 6530 mm x 2440 mm)
Note
The dimensions provided are for a system that uses a wall-mounted
reflector wall. For systems that use a free-standing reflector wall,
increase the minimum depth from 21’ 5” (6530 mm) to 22’ 1”
(6730 mm).
Lighting
Shoulder Light: No more than twice the facial light (measured on the
horizontal plane)
Note
This is lighting for 30 frames per second (FPS) conferences. 60 FPS
conferences may require additional lighting.
Acoustics
Ambient Noise
•
45dBA SPL
•
NC30
Reverberation:
•
150-700 ms for non-critical voice frequencies (>500 Hz, or <2 kHz)
•
150-500 ms for critical voice frequencies (500 Hz-2 kHz)
Acoustic panels on the side walls are required. For more information, see
the
“Acoustic Considerations For the TX9200” section on page 2-21
Power
2.93 kW required
Participant convenience ports consume additional power (maximum of
4.32 kW for 18 particpants)
HVAC
Independent Room Control
Typical Cooling 12,800 BTU/Hr
Design
Aesthetic Continuity highly desirable
For best video quality:
•
Avoid high contrast elements such as very dark or bright colors
•
Avoid glossy finishes
•
Avoid clutter
For more information, refer to the
Cisco TelePresence Wall Color Guide