- 35 -
・
This procedure becomes a system called target SV system that
exists in target specifications.
In option there is a thing called slope SV system. In case of this
system, set in 'SV' the SV variation quantity for each unit time. and
set the time in 'TIME' until which that SV variation can continue.
・
Combine with the desired program pattern and when you want to exit
the setting, set 'END/LINK00' in TIME of last step number and thus
end the pattern setting. In the initial setting status 'END/LINK00' is
always set in the last step.
・
When you want to link (link another pattern) a pattern, set the pattern
number that is to be linked, in '00' on the right of LINK of
'END/LINK00'of the last step. When link several patterns and link
form end pattern to first pattern, or set one of the pattern linked
itself, become endless (endless loop). Then pattern repeat is not
effected.
・
If you want to delete a certain step, set 'STEPDELETE' in TIME of
step number that is to be deleted. The contents of that step get
deleted and the step numbers from next step onwards are
automatically updated.
・
If you want to insert a certain step, set 'STEPINSERT' in TIME of
step number that is to be inserted. The contents which is same as
each parameter of selected step get inserted and the step numbers
from next step onwards are automatically updated.
3. Step repeat
①
Set step repeat.
②
It is a convenient function if you want to repeat a specific step
section in an identical pattern.
③
Set '00' in REPEAT of start repeat step number and set 'repeat
count' in REPEAT of end repeat step number. If 01 is set, the step
repeat section that is set is repeated once, hence the entire identical
step section is run twice.
④
In identical pattern, step repeat settings can be done any number of
times. However duplication of repeat section and, small repetitions
within large repetitions cannot be set.
When setting a number of sets of step repeat, set in such a way that
the '00' and repeat count settings always pair alternately in the
pattern.
⑤
On the upper right part of this setting screen, snap format of step
that is being set is displayed.
4. PID number and alarm
number
①
Set the PID number and alarm number for each pattern/step that
are set.
②
Set PID number from 1 to 9 and alarm number from 1 to 8.
Number 0 can also be set. When 0 is set, it becomes a function for
continuing with the same step number as that of the previous step.
5.A.R.W. number
①
Set ARWNo. For every pattern/step that is set.
②
Set it from numbers 1 to 8. Number 0 can also be set and when it is
set, a number same as that of the previous step is inherited. This is
the function.