- 77 -
[4-wire resistance thermometer]
No. Measurement range Scale range
(
°
C
)
Scale range
(K)
No. Measurement range Scale range
(
°
C
)
Scale
range
(K)
41
JPt100
Ω
1
-200.0 to 649.0
73.0 to 922.0
50
QPt100
Ω
5 -100.0 to 100.0
173.0 to 373.0
42
JPt100
Ω
2
-200.0 to 400.0
73.0 to 673.0
51
Pt50
Ω
-200.0 to 649.0
73.0 to 922.0
44
JPt100
Ω
4
-200.0 to 200.0
73.0 to 473.0
52
Pt-Co
4.0 to 374.0 K
4.0 to 374.0
45
JPt100
Ω
5
-100.0 to 100.0
173.0 to 373.0
53
Pt100
Ω
1
-200.0 to 850.0
73.0 to 1123.0
46
QPt100
Ω
1
-200.0 to 649.0
73.0 to 922.0
54
Pt100
Ω
2
-200.0 to 400.0
73.0 to 673.0
47
QPt100
Ω
2
-200.0 to 400.0
73.0 to 673.0
56
Pt100
Ω
4
-200.0 to 200.0
73.0 to 473.0
49
Resist
ance
thermometer
QPt100
Ω
4
-200.0 to 200.0
73.0 to 473.0
57
Resist
ance
thermometer
Pt100
Ω
5
-100.0 to 100.0
173.0 to 373.0
[Standard list]
K, E, J, T, R, S, B, N: IEC584 (1977,1982), JIS C 1602-1995, JIS C 1605-1995
WRe5-WRe26, W-WRe26, NiMo-Ni, Platinel
Ⅱ
, CR-AuFe, PtRh40-PtRh2: ASTM Vo1.14.03
U, L: DIN43710-1985
PR5-20: material of Johnson Matthey
Pt100: IEC751 (1995), JIS C 1604-1997
QPt100: IEC751 (1983), JIS C 1604-1989, JIS C 1606-1989
Ú
QPt100 is also called old PT100.
JPt100: JIS C 1604-1981, JIS C 1606-1986
Pt50: JIS C 1604-1981
10-2 .Linear scale
If linear input (DC voltage and current) is selected, initial value of linear scale and measurement scope is as
follows.
Measurement
range
Scale range
Measurement scope
(Initial value)
Linear scale (Initial
value)
31
10mV
- 10.0 to
10.0 mV
0.00 to 10.00
mV
0.0
to
2000.0
32
20mV
- 20.0 to
20.0 mV
0.00 to 20.00
mV
0.0
to
2000.0
33
50mV
- 50.0 to
50.0 mV
0.00 to 50.00
mV
0.0
to
2000.0
34 100mV -100.0
to
100.0
mV 0.0 to 100.0
mV
0.0
to
2000.0
35
5V
-5.0 to
5.0 V
0.000
to
5.000 V
0.0 to
2000.0
37 10V -10.0
to
10.0V
0.000 to
10.000V
0.0
to
2000.0
36 20mA
0.0
to
20.0
mA
4.00 to 20.00
mA
0.0
to
2000.0
Setting procedure is as follows.
①
For 'measurement scope' of mode 5, set the minimum value and the maximum value of the analog signal
that is actually input from the sensor.
②
For 'linear scale' of mode 5, after confirming how to display that minimum value and maximum value, set the
decimal point position and lower limit and upper limit of the scale.
③
For example, for 4 to 20 mA if you want to display 0.00 to 100.00, the settings are as follows.
・
Measurement scope : 4.000 (minimum value) to 20.000 (Maximum value).
・
Linear scale : DOT2.
0.00 (Lower limit) to 100.00 (Higher limit).