- 37 -
12. Subsidiary output number
①
It is displayed in specifications with transmission signal output when
transmission type 'SUB' is selected.
②
Set subsidiary output number for every pattern/step that is set.
③
Number 0 can also be set. When 0 is set,
it becomes a function that
inherits the same step number as that of the previous step.
13. SV scope
①
Set SV setting scope.
②
Setting scope is within the measurement scope (Including linear
scale).
③
When measurement range, unit, measurement scope, linear scale
etc is changed, sometimes setting range and decimal point position
changes or initialization takes place automatically and relatively
hence take care.
14. Pattern repeat
①
Set pattern repeat (repeat).
②
If you want to repeat the program pattern of same pattern number, it
is a very convenient function.
③
When '0001' is set, same pattern is repeated once. Hence on a
whole, the same pattern is run twice. 'Pattern repeat' is not only
applicable to the executing pattern, but this set value is always
enabled, hence take care.
15. Pattern clear
①
It is a function that clears (deletes) the pattern that is set.
②
When clearing the specified pattern number, set the pattern number
that is to be cleared, on the right side of 'EACH:' and click the
key.
③
When clearing all the pattern numbers that are set, move the cursor
to 'ALL' and click the
key.
④
When flashing is clear by clicking
key for while, and cursor retune
to “END”, clear (delete) is executed.
⑤
Executing pattern cannot be cleared.
⑥
Cleared pattern number cannot be restored, hence take care.
16. Pattern copy
①
It is a function of copying the optional pattern number that is set, in
pattern number which is not set.
②
Set the pattern number of copy source on the left side of and pattern
number of copy destination on the right side of '
→
', move the cursor
to 'YES' and click
key.
③
Copy function cannot be performed on the pattern number that is
set, hence if you want to copy on the pattern number that is already
set, clear that pattern and then copy.
17. Program reset SV
①
It is displayed in case of specifications with transmission signal
output or specifications with communication and when selecting
[TRANS] function.
②
Sets the SV at the time of resetting.
③
When selecting 'SV' by transmission type, the transmission value at
the time of resetting becomes this setting value.