- 59 -
6. Alarm output check
①
It is a check function of alarm output.
②
When this setting screen is displayed, the current alarm activation
status of alarm of 4 points is OFF. When select the alarm which
would like to ON and click
key, it become ON until selecting
OFF.
Using this function effectively facilitates the system checking of the
final product.
③
When this screen is removed, alarm output automatically returns to
current alarm activation status.
7. Time signal output testing
①
Displays only the instrument with external signal output (DO).
②
It is a testing function of time signal output.
③
When this setting screen is displayed, current activation status of
maximum 8 point time signal output become OFF automatically.
When select the time signal which make put in output status and
click the
key, become output status until selecting No.0 (NON).
Using this function effectively facilitates system checking of final
product.
④
When this screen is removed, time signal output automatically
returns to present activation status.
⑤
If do not allocate external signal, corresponded TS1 to 8 of upper
display are lighted in this function.
8. Checking status output
①
Displays only the instrument with external signal output (DO).
②
Check function of status output.
③
When this setting screen is displayed, current activation status of
maximum 5 point status become OFF automatically. When select
the status which make put in output status and click the
key,
become output status until selecting OFF.
④
When this screen is removed, status output automatically returns to
current activation status.
⑤
This function is effective only in the status output operation, and
program operation status and operation of display contents are not
changed.
Precaution
When setting screen of alarm output check, time signal output testing or
checking status output is displayed, present output status become
automatically OFF.
When it is troubled by becoming OFF, set “Lock” on mode screen. In case
of “Lock” setting, when each output check screen is displayed, present
output status is continued and not become automatically OFF.