- 90 -
10-9. Transmission signal output
It is a function that selects one type from PV (measurement value), SV (measurement value), MV1 (Output
value 1), MV2 (Output value 2), MFB (feedback value), SUB (subsidiary output) and outputs using analog signal.
Output 2 specifications of transmission signal output depending on the format are also available.
For example it is used in applications like, selecting a PV transmission and connecting that analog signal to
the recorder and recording the PV of this controller in the recorder. Specifications of analog signal are specified
in a format.
Sensor
(Controller
)
(Recorder)
The following occurs when transmission signal output with 4-20mA specified and measurement range K1 and
in a range of 0-1200
°
C transmits PV.
・
Set 'PV' in transmission type of mode and '0-1200' in 'transmission scale'.
T
ra
nsmissio
n sign
al outp
ut
(
0
%)
20mA
(
100
%)
(
50
%)
0 500
1200
(℃)
Transmission scale
12mA
4mA
Using PV transmission
record the PV in the
recorder
*Parallel connection of
sensor signal of
controller and recorder
is prohibited.
Consequently, PV
transmission shall be
ussed.