- 7 -
4-2. Mounting
4-2-1. Panel cutout and mounting method
1.
Usual mounting method
①
Insert this product in panel cutout.
②
Fit in the attached mounting bracket above and below and tighten the screws with the driver and fix it.
When the screws are tightened the torque is '0.6 – 0.8 Nm'.
③
For IP54 panel sealing specifications, confirm that the gasket between product and panels is correct.
Take care because if the gasket drifts or if there is a gap, the mounting is not proper and the water proofing
function does not work.
Panel cut
Unit: mm
2. Closed instrumentation
①
Insert this product in panel cutout.
②
Fit in the attached mounting bracket above and below and tighten the screws with the driver and fix it.
When the screws are tightened the torque is '0.6 - 0.8 Nm'.
③
At the time of closed instrumentation, even in the product of IP54 panel sealing specifications, as the
gasket functionality between the product and the panel is lost, water proofing functionality does not work.
Unit: mm
N: Number of mounted instruments
Panel cutout for closed instrumentation
120
120
92
+0.8
0
92
+0.8
0
Panel
Mounting
bracket
Controller
96×N-4
+2
0
92
+0.8
0