![background image](http://html.mh-extra.com/html/chino/kp-2000-series/kp-2000-series_instructions-manual_2602189034.webp)
- 31 -
13.SV correction
①
Sets SV correction (SV bias).
②
It is a function in which the entire SV is be shifted when you want to
shift executing SV a little and not just the setting of program pattern
is changed. This setting value is not only valid when SV correction
is in executing step, but is always valid. Hence take care.
③
When measurement range, unit, measurement scope, linear scale
etc is changed, sometimes decimal point position changes
automatically and relatively hence take care.
7-3. Mode 1
Mode 1 performs the setting related to run status.
Settings screen
Description of the screen
1. Mode screen
[Lock Status]
[Display OFF status]
①
Mode 1 screen.
②
By clicking the
・
key, 'Lock' and 'NoDisp' is displayed.
③
For mode 1 settings screen, if setting change is to be prohibited
select 'Lock'.
④
When doing the settings by communications, set all the mode
screens to 'Lock'.
⑤
When settings screen of mode 1 is not displayed, 'NoDisp' is
displayed.
2. Run operation key lock
①
Run operation key can be locked.
②
If 'UNLOCK' is selected, lock is released and
becomes enabled
and run operation can be done by key.
③
If 'LOCK' is selected, lock status,
key
is disabled and run
operation cannot be done by key.
3. Cancel alarm output
①
When canceling temporarily the alarm output that is activated, alarm
output is cancelled if 'RESET' is set.
②
At that time the cursor immediately returns to 'NON' and WAIT of
upper display window illuminates.
③
In cancel (WAIT) status, if you once drift away from alarm activation
condition, WAIT does not get illuminated and normal status returns.
④
Take care as the settings are common for alarm output of all the 4
points.
⑤
In case of specifications with external signal input, when canceling
using external signal input, it is done by external signal ON. After
cancellation immediately return the external signal to OFF.