- 39 -
4. Second output PID
①
Output 2 specifications and output 2 control are displayed only
when 'PID system' is selected.
②
Set the PID for output 2.
③
By setting P to 0%, it becomes two-position control operation.
④
If I is set to 0s, it is equivalent to
∞
and if D is set to 0s, it is
equivalent to OFF.
5. Second output gap
①
Output 2 specifications and output 2 control system is displayed
only when 'PID system' is selected.
②
Set the gap between output 1 and output 2.
6. Output dead band
①
Set output dead band.
②
Set PID dead band in 'PID D.BAND' of the upper row and output
dead band of two position control operation (When P=0%) in '
P=0
D.BAND
' on the lower row respectively.
③
PID dead band non-linearises the deviation in the dead band and
slows down the response of control output.
④
Output dead band of two position operation control action becomes
the dead band at the time of output ON/OFF.
7. Second output dead band
①
Output 2 specifications and output 2 control system are displayed
only when 'PID system' is selected.
②
Set output dead band for output 2.
③
Set PID dead band in 'D.BAND' of upper row, and output dead band
of two position control action (When P=0%). in 'P=0 D.BAND' of
lower row respectively.
④
PID dead band non-linearises the deviation in dead band and slows
the response of control output.
⑤
Output dead band of two-position control action becomes a dead
band at the time of output ON/OFF.